Welcome to Jingjiang Zhicheng Metrologic Instrument Co.,Ltd China
Position:Home
  HES Series Transformer Tester

Conventional and Electronic CT and PT Calibrator Model: HES-1BX

Time:2022-6-16 10:51:00

Product picture:

Conventional and Electronic CT and PT Calibrator Model: HES-1BX

Product details:


1. Conventional Transformer Test Function

Features

Digital LCD display.

Automatically indicate polar and alarm in case of wrong polarity.

Its built-in self-test circuit can monitor the precision of instrument itself.

Easy in operation, fast in measurement, compact in design, suitable for field test.

It can test for conventional voltage transformers according to IEC 61869-3, IEC 61869-5 standards.

It can test for conventional current transformers according to IEC 61869-2 standard.

Voltage measurement range: 0 ~ 300 V

Current measurement range: 0.05 A ~ 10 A

Ratio error of conventional voltage transformer and current transformer: ≤ ± 1.0% reading (display value)

Phase angle error of conventional voltage transformer and current transformer: ≤ ± 0.2 min.

2. Electronic Transformer Test Function

Introductions

Electronic transformer calibrator is mainly used to calibrate the electronic transformer that complies with IEC 61850-9-1, IEC 61850-9-2, IEC 61850-9-2LE standards. Calibration includes: ratio error, phase displacement, delay, polarity, etc. Equipped with small-signal input terminal, it can calibrate the small-signal output of the electronic transformer as well as the small-signal input merged unit, etc.

Display: TFT LCD touch screen with resolution 800x600 pixels.

 

 

Main features:
It can test for electronic voltage transformers (having an analogue output or a digital output): test according to IEC 61850-9-1, IEC 61850-9-2, IEC 61850-9-2LE standards.

It can test for electronic current transformers (having an analogue output or a digital output): test according to IEC 61850-9-1, IEC 61850-9-2, IEC 61850-9-2LE standards.

Test items included: ratio difference, phase difference, delay, polarity, etc..

Packets full frame resolution protocol of IEC 61850-9-1, IEC 61850-9-2, IEC 61850-9-2LE standards automatic analysis of ASDU (Application Service Data Unit) number and sampling points etc., all channel waveform display without capture can be intuitive to view all the channels of data.
Functions:

1. Verification of electronic voltage transformers (with analogue output).

2. Verification of electronic current transformers (with analogue output).

3. Verification of electronic voltage transformers (with digital output).

4. Verification of electronic current transformer (with digital output).

5. Test according to IEC 61850-9-1, IEC 61850-9-2, IEC 61850-9-2LE standards.

Technical specifications:

Ratio error: ≤ ± 0.05%

Phase angle error: ≤ ± 2 min.

Voltage measure range: 2 V ~ 300 V

Current measure range: 0.05 A ~ 10 A

Small signal voltage: 22.5 mV ~ 6.5 V

Communication protocol: IEC 61850-9-1, IEC 61850-9-2, IEC 61850-9-2LE standars